btu ton hp kw Featured Image

BTU to HP | BTU to Ton | BTU to kW | Conversion Tables

Many people get confused about BTU, Ton, HP, and kW used in air conditioning. What are they and what are their differences?

BTU, Ton, HP, and kW are the different units of measurement for the cooling capacity of an air conditioner. Most people refer to the cooling capacity of an air conditioner as BTU and Ton while some people prefer to use HP and kW when referring to the cooling capacity of an air conditioner.

Although all 4 units of measurement are referring to the same thing, each unit has a different number and they are all interchangeable through conversion. You also can use the below calculator to find the air conditioning horsepower for a given BTU or kW.

BTU to HP Calculator

Enter the cooling capacity of your air conditioner in BTU (or btu/hr) to calculate the equivalent air conditioning horsepower:

Cooling Capacity
BTU (or btu/hr)

Note: One air conditioning horsepower is approximately 9,000 BTU. However, horsepower is not an accurate representation of the cooling capacity. Read the explanation here.

kW to HP Calculator

Enter the cooling capacity of your air conditioner in kilowatt (kW) to calculate the equivalent air conditioning horsepower:

Cooling Capacity
kW

Note: The kW used here is not the power consumption of the air conditioner. In some places, the cooling capacity of air conditioners is expressed in kW. One kW is equivalent to 3412 BTU and one horsepower is equivalent to 9000 BTU. That makes one kW equal to 0.379 HP.

BTU to Ton Calculator

Enter the cooling capacity of your air conditioner in BTU (or btu/hr) to calculate the equivalent air conditioning tonnage (refrigeration ton):

Cooling Capacity
BTU (or btu/hr)

Note: One ton of refrigeration is equivalent to 12,000 BTU of cooling capacity. Learn what is Ton or refrigeration tonnage here.

Cooling Capacity Conversion Tables

Air conditioners come in standard capacity. The following tables show the unit conversions from BTU and HP to Ton and kW. The figure in the main unit column is the typical cooling capacity in air conditioner while the subsequent figures in the equivalent unit columns are based on mathematical conversions.

  • 1 kW = 3,412 BTU
  • 12,000 BTU = 1 Ton
Main Unit (BTU)Equivalent HPEquivalent TonEquivalent kW
9,000 BTU1.0 HP0.75 Ton2.63 kW
12,000 BTU1.5 HP1 Ton3.51 kW
18,000 BTU2.0 HP1.5 Ton5.27 kW
24,000 BTU2.5 HP2. Ton7.03 kW
30,000 BTU3.0 HP2.5 Ton8.79 kW
36,000 BTU3.5 HP3 Ton10.55 kW
From BTU to Other Units
Main Unit (HP)Equivalent BTUEquivalent TonEquivalent kW
1.0 HP8,500 – 9,500 BTU0.70 – 0.79 Ton2.49 – 2.78 kW
1.5 HP11,500 – 12,500 BTU0.95 – 1.04 Ton3.37 – 3.66 kW
2.0 HP17,500 – 18,500 BTU1.45 – 1.54 Ton5.12 – 5.42 kW
2.5 HP20,500 – 22,500 BTU1.70 – 1.87 Ton6.00 – 6.59 kW
3.0 HP24,000 – 30,000 BTU2 – 2.5 Ton7.03 – 8.79 kW
3.5 HP32,000 – 36,000 BTU2.67 – 3 Ton9.38 – 10.55 kW
From HP to Other Units
Main Unit (Ton)Equivalent BTUEquivalent HPEquivalent kW
1 Ton12,000 BTU1.5 HP3.51 kW
1.5 Ton18,000 BTU2.0 HP5.27 kW
2 Ton24,000 BTU2.5 HP7.03 kW
2.5 Ton30,000 BTU3.0 HP8.79 kW
3 Ton36,000 BTU3.5 HP10.55 kW
4 Ton48,000 BTU5.0 HP14.1 kW
5 Ton60,000 BTU6.5 HP17.6 kW
From Ton to Other Units
Main Unit (kW)Equivalent BTUEquivalent HPEquivalent Ton
2.5 kW8,530 BTU1.0 HP0.71 Ton
3.5 kW11,942 BTU1.5 HP0.99 Ton
5.0 kW17,060 BTU2.0 HP1.42 Ton
7.1 kW24,225 BTU2.5 HP2.01 Ton
9.0 kW30,708 BTU3.0 HP2.56 Ton
From kW to Other Units

As you can see, a standard 9000 BTU air conditioner is equivalent (not mathematically) to a 1.0 horsepower air conditioner which is also equal to a 2.5 kW and a 0.75-ton air conditioner.

Want to Learn HVAC in a More Structured Way?

This article explains one part of HVAC, but HVAC becomes much easier to understand when the topics are connected step by step. If you want a clearer learning path, explore my HVAC learning resources, including online courses, membership, corporate training, and 1-to-1 mentorship.

Need help with an actual project or system issue? View HVAC Engineering Services.

Common BTU Conversions

BTU is a widely used unit of measurement for the cooling/heating capacity of air conditioners. Although there is a fixed conversion rate, BTU conversions often meant for the conversion between the capacity of air conditioners.

So, the conversion result is more useful when present in terms of air conditioner capacity as follow:

BTU to kW Conversion

  • 9000 BTU is equivalent to 2.5 kW
  • 12000 BTU is equivalent to 3.5 kW
  • 18000 BTU is equivalent to 5.0 kW
  • 24000 BTU is equivalent to 7.1 kW

BTU to Ton Conversion

  • 9000 BTU is equivalent to 0.75 Ton
  • 12000 BTU is equivalent to 1 Ton
  • 18000 BTU is equivalent to 1.5 Tons
  • 24000 BTU is equivalent to 2 Tons
  • 30000 BTU is equivalent to 2.5 Tons

BTU to HP Conversion

  • 9000 BTU is equivalent to 1 HP
  • 12000 BTU is equivalent to 1.5 HP
  • 18000 BTU is equivalent to 2 HP
  • 24000 BTU is equivalent to 2.5 HP
  • 30000 BTU is equivalent to 3 HP

In Malaysia, we use all 4 units of measurements all the time and I find myself keep pressing on my calculator when I’m working on cooling capacity related work. So, what are they?

How to Convert BTU to HP?

BTU is the most common unit of measurement for the capacity of air conditioners. On the other hand, HP or horsepower is a common unit of measurement for the capacity of air conditioners in certain regions.

To convert BTU to HP, divide BTU by 9000.

Generally, BTU divided by 9000 equals HP. 9000 BTU divided by 9000 is 1 HP. When converting 12000 BTU to HP, round the resulted HP to 1.5 as it is the standard HP capacity for 12000 BTU air conditioners. Similarly, a 24000 BTU air conditioner is equivalent to a 2.5 HP air conditioner.

For compressor horsepower, we can divide BTU by about 8500-9000 to estimate the equivalent.

How to Convert BTU to Ton?

BTU and Ton are two commonly used units of measurement for the capacity of air conditioners depending on the regions. Ton is short form for refrigeration tonnage.

To convert BTU to Ton, divide BTU by 12000.

Mathematically, BTU divided by 12000 equals Ton. Hence 12000 BTU is equivalent to 1 Ton. Similarly, a 9000 BTU air conditioner is equivalent to a 0.75 Ton air conditioner. Meanwhile, a 3 Ton air conditioner is equivalent to a 36000 BTU air conditioner.

Btu/hr/sqft to W/sqm Conversion

Most of the time, btu/hr/sqft is the easier method used to estimate air conditioner size. Many of the HVAC resources are spelled in btu/hr. It posses a problem for SI unit users.

Take 60 btu/hr/sqft as an example. Here’s how to convert it into W/sqm:

Recalling that 1 kW = 3412 btu/hr. So,
60 btu/hr/sqft ÷ 3412 = 0.0176 kW/sqft

Since 1 kW = 1000 W,
0.0176 kW/sqft x 1000 = 17.6 W/sqft

Now, 1 m = 10.76 sqft. So,
17.6 W/sqft x 10.76 = 189.38 W/sqm.

If we divide 189.39 by 60, we get a conversion factor of 3.156. So now, whenever we multiply 3.156 by a number in btu/hr/sqft, we’ll convert it into W/sqm. For example:

  • 60 btu/hr/sqft x 3.156 = 189.36 W/sqm
  • 80 btu/hr/sqft x 3.156 = 252.48 W/sqm
  • 120 btu/hr/sqft x 3.156 = 378.72 W/sqm

With 3.156 being the conversion factor from btu/hr/sqft to W/sqm, you can now switch between the two at ease.

What is BTU in Air Conditioning?

BTU stands for British Thermal Unit. BTU is a measurement of heat energy. BTU is defined as the amount of heat required to raise the temperature of 1 lb of water by 1°F.

When using BTU to estimate the cooling capacity of an air conditioner, time must be factored in. For instance, one hour. In another word, how much heat energy needs to be released to reduce the temperature of 1 lb of water by 1°F in one hour?

Hence, BTU per hour or BTU/HR is the precise unit to use when referring to the cooling capacity of an air conditioner. However, most people use BTU or BTU/HR interchangeably when referring to the cooling capacity of an air conditioner.

In my opinion, BTU is the best measurement unit to use when comparing and calculating the cooling capacity required. BTU can be converted into both kW and Ton scientifically. Besides, BTU is the most commonly used measurement unit and thus, communication with other people is easier.

What is Ton in Air Conditioning?

Ton in air conditioning is an acronym for refrigeration ton (RT). Here, ton is not referring to weight when used to describe the cooling capacity of an air conditioner. Another variant of this is TR which stands for tons of refrigeration.

Refrigeration ton is defined as the rate of heat transfer required to melt 1 ton of pure ice at 0°C in 24 hours. The ton of pure ice is referring to the weight of the ice. Before people have modern air conditioners, they use ice to cool their houses and store their foods. Thus, refrigeration ton was used to measure the consumption of 1 ton of ice in one day.

Nowadays, refrigeration ton is still preferred by many people and it is mostly used in commercial air conditioning systems.

I use refrigeration ton (RT) for a large cooling capacity because BTU will be too long. For example, a 400RT chiller is equivalent to 4,800,000 BTU. Also, people are more difficult to understand long numbers.

What is HP or Horsepower in Air Conditioning?

HP or horsepower is a unit of measurement of power. Power is the amount of work done over a certain period of time. Horsepower is most commonly used to describe the power of an engine.

Initially, horsepower in air conditioning was referring to the rotational power of the motor in an air conditioner whereas back then it was a fairly good estimation of the resulting cooling capacity of the air conditioner.

Nowadays, horsepower is no longer a correct indication of the cooling capacity of an air conditioner. However, some people still use horsepower to refer to the range of cooling capacity of an air conditioner.

I think horsepower (HP) is the best when referring to residential air conditioners. Most people use home air conditioners and they don’t necessarily understand BTU and Ton.

Furthermore, they are often confused the kW for cooling capacity with the kW for power consumption. Horsepower is the simplest way to call the size of their air conditioners.

Why 1.0 HP is Equivalent to a Range of BTU?

Back then, air conditioner manufacturers use the rotational horsepower of the compressor motor as the indication of the cooling capacity of their air conditioners. Nowadays, this method is not applicable because it does not account for the efficiency of each component inside an air conditioner.

For example, two air conditioners with the same compressor motor can result in one air conditioner having a higher cooling capacity than the other due to better controls.

However, it doesn’t mean that if the same 1HP air conditioner but one has 8,500 BTU and the other has 9,500 BTU, the former one has poor efficiency. We need to compare them using the coefficient of performance (COP).

Nowadays, people still use horsepower as the indication of air conditioner cooling capacity probably because it is easier for most people to understand. However, BTU or kW or both are always included in the specification of an air conditioner even though the horsepower is stated.

What is kW or Kilowatt in Air Conditioning?

kW or kilowatt in air conditioning refers to two metrics: a) cooling capacity and b) power consumption. Kilowatt used for the cooling capacity of an air conditioner is derived from the heat transfer equation as follow:

heat transfer equation

Using kilowatt as the unit of measurement for the cooling capacity of an air conditioner is a convenient indicator of the efficiency of the air conditioner as it is the same unit of measurement as the input electrical power. However, don’t get confused with their unit of measurement as they are two very different metrics.

specs 6.3kw 9.5kw

Whenever I calculate the efficiency of an air conditioner, I’ll convert BTU to kW because the coefficient of performance (COP) is calculated by dividing the output by the input (cooling capacity/power consumption). In another word, it’s kW/kW.

If you are new to air conditioning and you’re not sure what are some of the other parameters written in the spec sheet, you can understand them from my article: How to Read Air Conditioner Specifications (12 Specs!).

Preference of Measurement Units for Cooling Capacity around the World

The unit of measurement used for the cooling capacity of an air conditioner is based on the preferences and practices of people in a particular region.

units used around the world 1200

Based on the data that I’ve gathered, it seems like most of the countries prefer to use BTU and Ton when indicating the cooling capacity of an air conditioner. Some countries prefer to use HP and a few countries used kW to refer to the cooling capacity of an air conditioner.

Nevertheless, it doesn’t matter which measurement units we used as long as we can understand it.

Build Your HVAC Knowledge with a Structured Learning Path

If this guide helped you understand the topic, the next step is to learn HVAC in a more organized way. The HVAC Learning Hub helps you choose the right path based on your goal, whether you want self-paced courses, membership access, corporate training, or 1-to-1 mentorship.

Need project-specific advice, design, or troubleshooting support? View HVAC Engineering Services.

FAQs

1. What is the difference between BTU, Ton, HP, and kW in HVAC?

BTU (British Thermal Unit) measures heat energy, Ton is a cooling capacity unit (12,000 BTU/hr), HP (Horsepower) is used for motor power, and kW (kilowatt) is a metric unit for electrical power. Each represents different aspects of HVAC performance.

2. How do I convert BTU to Ton?

Use this formula:
1 Ton = 12,000 BTU/hr
So, divide the BTU value by 12,000 to get Tons.
Example: 36,000 BTU/hr = 3 Tons

3. How do I convert kW to Ton?

Use the conversion:
1 kW ≈ 0.284 Tons
To convert, multiply kW by 0.284.
Example: 10 kW × 0.284 = 2.84 Tons

4. What is the formula to convert HP to kW?

The standard formula is:
1 HP ≈ 2.637 kW
Multiply HP by 2.637 to get the kW value.
Example: 5 HP × 2.637 = 13.18 kW

5. Why do HVAC systems use different units?

BTU and Ton are commonly used in North America to express cooling capacity, while kW is more standard internationally. HP is typically used to describe the power of motors in compressors or fans while also used to express cooling capacity due to habit.

6. Is there a quick chart for converting between units?

Yes! This article includes a conversion table showing relationships between BTU/hr, Ton, HP, and kW for quick reference.

Leave a Reply

Your email address will not be published. Required fields are marked *

This site uses Akismet to reduce spam. Learn how your comment data is processed.

5 Comments

  1. Explanation is very nice and simple to understand. But I have some confusionin point number 4 converting HP to Kw

    1. The 1 HP = 2.637 kW is actually a shortcut. Basically, we always want to convert the unit into BTU/HR then convert to whatever unit we need. Eg: 1 HP = 9000 BTU/HR and then 9000 / 3412 = 2.637 kW. So 1 HP = 2.637 kW of cooling capacity