How Many Square Feet a 3 Ton Air Conditioner Cools

How Many Square Feet a 3-Ton Air Conditioner Cools?

A 3-ton air conditioner is one of the most common air conditioner sizes used in homes. It can be used to cool a single room or an entire house. So, how many square feet a 3-ton air conditioner cools?

Generally, a 3-ton air conditioner can comfortably cool a 1500 square feet room. For an entire house, a 3-ton air conditioner is usually sufficient for a 2000 sqft insulated house. On the upper limit, a 3-ton air conditioner can cool a house with a floor area up to 2400 sqft.

How many square feet a 3-ton air conditioner cools is depending on several factors. Homeowners don’t really want to do engineering calculations. So, I made a few examples.

Is a 3-Ton Air Conditioner Enough?

To give you an idea about whether a 3-ton air conditioner is enough for your house, I prepared a house plan of 3 common types of single-family houses with different floor areas.

Take note that the following examples of cooling capacity calculation are assumed that the house is insulated. For non-insulated houses, the cooling capacity needed could be doubled.

1800 Sqft Double Story Country House

1800 Sqft Double Story Country House Photo

A typical 1800 sqft double-story country house usually has a large garage, dining room and family room with 3-4 bedrooms. Although it has 1800 sqft of total floor area, the total square footage required for cooling maybe around 1080 only, excluding the garage.

Following is the floor plan of a typical double-story 1800 sqft country-style house:

1800 Sqft Double Story Country House First Floor Plan Floor Area
First Floor
1800 Sqft Double Story Country House Second Floor Plan Floor Area
Second Floor

For most people, the bathroom, hallway and stairs don’t need dedicated air conditioning. So, we don’t have to include the floor area of these spaces in our air conditioner size calculation.

Furthermore, the garage often demands much greater cooling than the rest of the house. Besides, some houses don’t have ductwork in the garage. Hence, most people opt for a separate air conditioning system such as the mini split system for the garage.

Therefore, we are left with the dining room, family room, flex room (if got) and bedroom.

Below is a summary of the cooling capacity needed for each room:

RoomFloor AreaCooling Capacity Needed
Dining and Family Room410 sqft16300 BTU
Flex Room120 sqft2400 BTU
Master Bedroom210 sqft5250 BTU
Bedroom 2120 sqft3000 BTU
Bedroom 3110 sqft2750 BTU
Bedroom 4110 sqft2750 BTU
Total1080 sqft32450 BTU

Since the dining room and the family room have no partition wall in between, they can be combined into one large space. Furthermore, there are several kitchen appliances in the room and thus, an additional 4000 BTU cooling capacity is needed.

Assume that the house has a standard 9 ft tall ceiling. So, we don’t need to add more cooling capacity to accommodate the extra space.

We usually use about 20-30 BTU per square foot to calculate the cooling capacity needed for each room. If we expect to hold more people (eg: 4-6 people) at once, then we use 30 BTU per square foot. For small and windowless rooms, we use 20 BTU per square foot.

Moreover, if a room has many windows or the sunlight coming in the room is very strong in the afternoon, we also use a higher value of BTU per square foot (eg: 25 or 30) for the calculation.

So, to calculate the cooling capacity needed for each room, multiply the BTU per square feet value by the floor area (square footage) of the room.

For example, the master bedroom has 210 sqft of floor area. By using 25 BTU per square foot, the cooling capacity needed is 5250 BTU.

Now, the total cooling capacity needed for the above 1800 sqft country house is 32450 BTU which is exactly 2.7 tons given that one ton is equivalent to 12000 BTU.

But, it is rare to have an exact 2.7-ton air conditioner on the market. Most of the time, the cooling capacity of the air conditioner in this case is either 2.5 tons or 3 tons.

Personally, I would pick a 3-ton air conditioner with inverter technology (variable speed). With inverter technology, a 3-ton air conditioner usually can operate at anywhere between 12000 BTU and 36000 BTU depending on the model.

As a result, if I don’t need that much cooling, my 3-ton air conditioner can reduce its cooling capacity and therefore, my house won’t be too cold and I can save energy too.

Meanwhile, my 3-ton air conditioner has sufficient cooling capacity to keep my house cool and comfy during exceptionally hot days (over 100°F).

So, a 3-ton air conditioner is feasible if you have an 1800 sqft double story country house similar to the above example.

2000 Sqft Double Story Craftsman House

2000 Sqft Double Story Craftsman House Photo 1

A typical 2000 sqft double story craftsman house has a large garage and plenty of bedrooms. Although it is a 2000 sqft house, the total floor area that required cooling is often around 1650 sqft only, excluding the garage.

Following is the floor plan of a typical 2000 sqft double story craftsman-style house:

2000 Sqft Double Story Craftsman House First Floor Plan Floor Area 1
First Floor
2000 Sqft Double Story Craftsman House Second Floor Plan Floor Area
Second Floor

For most people, again the bathroom, hallway and stairs don’t need dedicated air conditioning. So, we can exclude the floor area of these spaces from our air conditioner size calculation.

Furthermore, the garage often demands much greater cooling than the rest of the house. Besides, some houses don’t have ductwork in the garage. Hence, most people opt for a separate air conditioning system such as the mini split system for the garage.

Therefore, we are left with the family room, kitchen, dining room, breakfast room, media room and bedroom.

Below is a summary of the cooling capacity needed for each room:

RoomFloor AreaCooling Capacity Needed
Family Room330 sqft8250 BTU
Dining140 sqft2800 BTU
Kitchen and Breakfast Room270 sqft6750 BTU
Master Suite220 sqft5500 BTU
Bedroom 2130 sqft2600 BTU
Bedroom 3140 sqft2800 BTU
Bedroom 4220 sqft4400 BTU
Media Room200 sqft4000 BTU
Total1650 sqft37100 BTU

Since there is no partition wall in between the breakfast room and kitchen, they can be combined into one large room. Still, notice that the cooling capacity of each room is slightly lower compared to the first example.

The cooling capacity needed for each room is really depending on factors such as the number of people, solar heat gain from windows and the heat emitted by electrical appliances and lighting. So, we need to decide on any figure between 20-30 BTU per square foot.

Furthermore, if the house is well-insulated, we also can reduce the cooling capacity needed for each room. Hence, older houses often need more cooling capacity to achieve the same cooling effect due to insulation degradation.

Now, the total cooling capacity needed for the above 2000 sqft double story craftsman house is 37100 BTU or about 3.1 tons given that one ton equals 12000 BTU.

However, there is no exactly 3.1-ton air conditioner on the market. So, we can either go for a 3.5-ton air conditioner or use a 3-ton air conditioner to save cost.

If you’re living in a place where the outdoor temperature barely exceeds 95°F during the summer, you can consider putting a 3-ton air conditioner in a 2000 sqft house like the above example.

Most air conditioners have their cooling capacity rated based on an outdoor temperature of 95°F. The higher the outdoor temperature, the lower the cooling capacity and vice versa.

2400 Sqft Double Story Farmhouse

2400 Sqft Double Storey 3 Beds 2.5 Baths Farmhouse House Photo

A typical 2400 sqft double story farmhouse may have a very large built-up area but the room size is quite similar to a 2000 sqft craftsman house or even an 1800 sqft country house. The total floor area that needs cooling maybe around 1660 sqft only.

Following is the floor plan of a typical 2400 sqft double story farmhouse:

2400 Sqft Double Story Farmhouse First Floor Plan Floor Area
First Floor
2400 Sqft Double Story Farmhouse Second Floor Plan Floor Area edited
Second Floor

For an even bigger size house, there are even more rooms that don’t require cooling. These rooms can be excluded such that a 3-ton air conditioner is sufficient to cool the entire house.

However, putting a 3-ton air conditioner in a 2400 sqft house is on the upper limit. During hot days, certain rooms (especially those that have a lot of windows) may not have sufficient cooling.

Below is a summary of the possible cooling capacity for each room:

RoomFloor AreaCooling Capacity Needed
Great Room320 sqft8000 BTU
Dining and Kitchen350 sqft8750 BTU
Master Bedroom220 sqft4400 BTU
Closet140 sqft2800 BTU
Bedroom 2150 sqft3000 BTU
Bedroom 3150 sqft3000 BTU
Bedroom 4230 sqft5750 BTU
Flex Room100 sqft2000 BTU
Total1660 sqft37700 BTU

Most of the rooms are given 20 BTU per square foot of cooling capacity. Hence, if there is more people in the room or the sunlight coming in the room is very strong, insufficient cooling problems may occur.

However, such a design is not wrong and is often considered as efficient because we are sizing the air conditioner based on the condition we expect to get most of the time.

Furthermore, we can opt-out of the need for cooling unnecessary rooms such as the closet. Hence, we can have more cooling capacity for other rooms.

Putting a 3-ton air conditioner in a 2400 sqft double-story farmhouse is not impossible. But, you should expect to have a blind/curtain on all windows. Besides, the insulation of the house is expected to be in a good condition.

Furthermore, the 3-ton air conditioner may not be able to give you too low of a room temperature such as 70°F. Moreover, the installation quality must be very good as there is not much room for mistakes.

Final Thought

For a room, the calculation of the cooling capacity needed is straightforward. For homeowners, just multiply a figure anywhere between 20-30 BTU per square foot by the square footage of the room to get the cooling capacity needed.

For a house, you need to decide which room needs cooling. Then, calculate the square footage of each room and obtain the cooling capacity needed by multiplying it by a figure anywhere between 20-30 BTU per square foot.

When deciding on a figure between 20-30 BTU per square foot, you need to account for the heat gain from various sources such as people, electrical appliances, lighting and windows. If you think that the room is going to be a lot hotter than other rooms, use a higher BTU per square feet value.

The cooling capacity calculation is always an estimation. Even with sophisticated heat load calculation software, engineers often lack various information and they fill the gap with assumptions most of the time.

Finally, putting an air conditioner with a slightly bigger cooling capacity (eg: one size bigger) is always better than not having sufficient cooling later on. However, the initial cost is also an important consideration.

Lastly, consider my Mini Split (eBook) if you want to know how can you use Mini Split in your house. If you still have doubt or not feeling confident enough, feel free to consult me.

Consultation Service

Ask me for HVAC advice such as brand selection, best model, benefits, features, placement, duct size, grille size, how to design, design check, verification and other HVAC related queries.

Leave a Reply

Your email address will not be published. Required fields are marked *

This site uses Akismet to reduce spam. Learn how your comment data is processed.