  1. Hi, Yu
    I just have a question about the pump head loss calculation:
    Do we need to consider the height of the furthest equipment, such as FCU(if it is located at 20/FF of the building and the pump is located in G/F), in the closed loop system? I mean the pump also need to “push” the water to overcome the resistance given by the gravity.

    Does the pump head loss per meter calculated by the Hazen-Williams Equation already represent the case in “vertical distance” head loss I mentioned above?

    1. In close loop systems there is no need to include the vertical height because the return side (which is also vertical, downward) cancel out the supply side. You only need to account for the friction loss and equipment pressure drop.