How to Calculate Static Pressure in a Duct

How to Calculate Static Pressure in a Duct?

A fan must have enough external static pressure to deliver the required airflow in a duct system. Hence, the static pressure in the duct must be determined. So, how do you calculate static pressure in a duct?

To calculate the static pressure in a duct, add the pressure loss due to straight ducts, duct fittings such as elbow, reducer and tee, and the pressure loss due to equipment including dampers and grilles. Select a fan that has an external static pressure greater than the static pressure in the duct.

Static pressure in a duct is calculated differently based on whether it is a straight duct, fitting or a piece of equipment like a damper. So, let’s take a closer look at how the static pressure in a duct is calculated.

Duct Static Pressure Calculation

Static pressure in a duct is the amount of pressure in the duct when the fan is not running. All fans have a certain amount of static pressure that we often call ESP (external static pressure).

On the flip side, internal static pressure is the strength of the fan needed to overcome its own internal component air resistances and this is taken care of by the fan manufacturer. For us (engineer / technician / homeowner), we just need to select a fan that has an ESP more than the static pressure in the duct.

As a fan moves the air, it creates pressure and this pressure gradually decreases as the air moves further away from the fan. This pressure decrease is due to the air resistance of the internal surface of the duct, duct fittings (elbow, reducer, etc.) and equipment (damper, grille, etc.)

The air resistance due to these duct components is commonly known as pressure loss or pressure drop or static loss or friction loss. Therefore, to calculate the static pressure in a duct, we need to find out the pressure loss due to straight ducts, duct fittings and equipment.

For straight ducts, we can use the Darcy friction loss equation to calculate the pressure loss. For duct fittings, we need to refer to the ASHRAE Duct Fitting Database (DFDB) to find the pressure loss of different duct fittings under different conditions since there are hundreds of them. Finally, the equipment pressure loss is obtained from the manufacturer.

Duct static pressure calculation is a lengthy and complicated process. However, I’ll break it down for you in a step-by-step manner so that you can understand it.

Duct Static Pressure Formula

The friction loss of straight ducts can be calculated using the Darcy friction loss equation. For duct fittings, the loss coefficient must be determined.

Darcy Friction Loss Equation (Straight Ducts)

The Darcy friction loss equation can be used to calculate the static pressure of straight ducts and plenum boxes. It is expressed as follows:

Dpf = f(1000/Dh)(0.5ρV2)L

where,
Dpf = Darcy friction loss in terms of total pressure, Pa
f = Friction loss factor
Dh = Hydraulic diameter, mm
ρ = Density of air, 1.204 kg/m3 at 20°C
V = Velocity, m/s
L = Duct length, m

The Darcy friction loss equation requires inputs that involved several more formulas. At a glance, it seems complicated but I’ll break it down for you.

Hydraulic Diameter, Dh

From the Darcy friction loss equation, the hydraulic diameter (Dh) is calculated using the formula:

Dh = 4A/P

where,
Dh = Hydraulic diameter, mm
A = Area, mm2
P = Perimeter, mm

The hydraulic diameter requires the area and the perimeter of the duct. For rectangular ducts, the area is simply duct width times duct height and the perimeter is duct width plus duct height times 2.

Arectangular = Width x Height
Prectangular = (Width+Height) x 2

For round ducts, the area is πr2 and the perimeter is 2πr.

Around = πr2
Pround = 2πr

After the hydraulic diameter, we also need to calculate the velocity.

Velocity, V

The velocity (V) used in the Darcy friction loss equation is calculated using the formula:

V = Q/A

where,
Q = Flow rate, m3/s
A = Area, m2

Hence, the airflow rate and duct size are the two basic pieces of information needed to calculate the static pressure in a duct. But, we’re not done yet.

Reynolds Number, Re

The Reynolds number (Re) needed in the friction factor equation is calculated using the formula:

Re = VDh/(1000v)

where,
V = Velocity, m/s
Dh = Hydraulic diameter, mm
v = Kinematic viscosity of air, 0.00001516 m2/s at 20°C

The kinematic viscosity of air is determined by the properties of air, just like the density of air. However, both values are based on a set air condition. In the case of duct static pressure calculation, the properties of air are set at 1 atmospheric pressure at 20°C.

Friction Loss Factor, f

The friction factor (f) is calculated using the formula:

f’ = 0.11(e/Dh+68/Re)0.25

where,
f’ = Initial friction loss factor
Dh = Hydraulic diameter, mm
Re = Reynolds number
e = Duct absolute roughness factor, mm

The friction loss factor is another sub-equation in the Darcy friction loss equation. I use f’ and f to separate the initial and final friction loss factor because it has a rule as follows:

If f’ ≥ 0.018, then f’ = f. Else, f = 0.85f’+0.0028

The duct absolute roughness factor (e) is published by ASHRAE in the ASHRAE Handbook of Fundamentals under the same chapter of Duct Design:

duct absolute roughness factor
Duct Absolute Roughness Factor

Generally, for galvanized iron (GI) ducts, either round or rectangular, the roughness factor is 0.09 mm. For flexible ducts, the roughness factor is 3.0 mm. Another common type of duct is fiberous glass duct which a roughness factor is 0.9 mm.

With the Darcy friction loss equation and its associated formulas, we can calculate the static pressure of straight ducts and plenum boxes. Next, we’ll look at the formula used to calculate the static pressure of duct fittings.

Dynamic Pressure and Loss Coefficient (Duct Fittings)

The dynamic pressure formula multiplied by the duct fitting loss coefficient is the pressure loss of the duct fitting. It is expressed as follows:

PL = PvCo
PL = 0.5ρV2Co

where,
PL = Pressure loss, Pa
Pv = Dynamic pressure, Pa
ρ = Density of air, 1.204 kg/m3 at 20°C
V = Velocity, m/s
Co = Fitting Loss Coefficient

We need to identify the type of duct fitting in the duct system and use the corresponding loss coefficient listed in the ASHRAE database to calculate the pressure loss.

Want to Learn HVAC in a More Structured Way?

This article explains one part of HVAC, but HVAC becomes much easier to understand when the topics are connected step by step. If you want a clearer learning path, explore my HVAC learning resources, including online courses, membership, corporate training, and 1-to-1 mentorship.

Need help with an actual project or system issue? View HVAC Engineering Services.

Duct Static Pressure Calculation Example

Now that we’ve gone through all the equations and formulas used to calculate duct static pressure, let’s use an example and I’ll show you how to calculate the static pressure of the duct system.

Below is a diagram showing the duct layout of a simple fresh air system:

duct static pressure calculation example
Duct Static Pressure Calculation Example

From the above diagram, 3 pieces of equipment are marked in bold (fresh air louver, fresh air fan and fresh air grille). The goal is to find out the external static pressure needed for the fresh air fan to deliver 500 CMH at the fresh air grille.

Equipment Pressure Loss

Equipment such as damper, grille and diffuser have pressure loss. The pressure loss of the above external louver and the grille can be estimated as follows:

Fresh Air Louver = 50 Pa
Fresh Air Grille = 25 Pa

Equipment pressure loss is obtained from the manufacturer’s performance data. However, in the early design stage, we yet to finalize the actual brand and model to be used. Hence, we can use estimation first and then assess if a re-calculation is needed when the materials are confirmed.

Straight Ducts and Plenum Box Pressure Loss

The duct sections marked in blue color are straight ducts and plenum boxes that we can use the Darcy friction loss equation to calculate their pressure losses. Take section 2 (plenum box) as an example, the pressure loss can be calculated as follows:

Flow Rate, Q = 500 CMH = 0.139 m3/s
Area, A = 350 x 350 = 122,500 mm2 (0.1225 m2)
Perimeter, P = (350+350) x 2 = 1400 mm2
Length = 0.2 m

Hydraulic Diameter, Dh = 4A/P = 4(122500)/1400 = 350 mm
Velocity, V = Q/A = 0.139/0.1225 = 1.13 m/s
Reynolds Number, Re = VDh/(1000v) = (1.13×350)/(1000×0.00001516) = 26088

Next is the friction loss factor and the plenum box is made of galvanized iron (GI), the absolute roughness factor (e) is 0.09mm and therefore:

Friction Loss Factor, f’ = 0.11(e/Dh+68/Re)0.25
Friction Loss Factor, f’ = 0.11(0.09/350+68/26088)0.25
Friction Loss Factor, f’ = 0.0254

Since f’ ≥ 0.018, f’ = f and thus, f = 0.0254.

Now, put everything into the Darcy friction loss equation:

Dpf = f(1000/Dh)(0.5ρV2)L
Dpf = (0.0254)(1000/350)(0.5)(1.204)(1.132)(0.2)
Dpf = 0.01 Pa

Using the same calculation process, the pressure loss in other straight duct sections can be determined. The below table shows the calculation result:

Duct SectionPressure Loss
20.01 Pa
41.47 Pa
60.49 Pa
90.25 Pa
112.46 Pa
131.78 Pa
Total6.46 Pa

Duct Fitting Pressure Loss

From the earlier diagram, duct fittings are marked in red color. To find the loss coefficient, we need to identify the duct fitting type. Take section 5 (90° elbow) as an example, its loss coefficient can be determined as follows:

Duct Section 5: 90° Elbow
ASHRAE Fitting Code: CR3-1 | Elbow, Smooth Radius, Without Vanes

ASHRAE duct fitting code CR3-1

Assume that the radius (r) is 250 mm, then r/W = 1.0 which means the Cp value is 0.23. Since it is a 90° elbow, the angle factor (K) is 1.00. Therefore, the loss coefficient (Co) of this duct elbow is 0.23.

If the same duct elbow only has 45°, applying the angle factor of 0.60 will result in a loss coefficient (Co) of 0.138.

The loss coefficient table shown above is extracted from the 2009 ASHRAE Handbook of Fundamentals. However, it is incomplete. The complete version needs to be purchased from ASHRAE. The mobile app version is very handy but it comes with a cost.

With the loss coefficient, the pressure loss of the 90° elbow can be calculated as follows:

Velocity, V = Q/A = 0.139/0.05 = 2.78 m/s

Pressure Loss, PL = 0.5ρV2Co
Pressure Loss, PL = (0.5)(1.204)(2.782)(0.23)
Pressure Loss, PL = 1.07 Pa

Following the same process, the pressure loss in other duct fittings can be determined. The below table shows the result:

Duct SectionDescriptionFitting CodeLoss CoefficientPressure Loss
3ReducerSR4-20.060.28 Pa
590° ElbowCR3-10.231.07 Pa
7Square to Round Connector
(Fan Inlet)
ER4-30.231.07 Pa
8Round to Square Connector
(Fan Outlet)
SR4-31.306.05 Pa
1090° ElbowCR3-10.231.07 Pa
12Flexible Duct CollarSR5-111.4016.49 Pa
14Round to Square Connector
(Diffuser)
SR4-327.9012.68 Pa
Total38.71 Pa

Total Static Pressure

Now, let’s summarize what we have and what we’ve calculated so far:

  • Equipment Pressure Loss: 75 Pa
  • Straight Duct Pressure Loss: 6.46 Pa
  • Duct Fitting Pressure Loss: 38.71 Pa

For straight ducts and duct fittings that undergo a complex calculation and selection process, a 15% safety factor can be given. Hence, the total static pressure can be calculated as follows:

Total Static Pressure = Equipment + Straight Duct + Duct Fitting
Total Static Pressure = 75 Pa + (6.46 x 1.15) + (38.71 x 1.15)
Total Static Pressure = 127 Pa

Since the duct system has a static pressure of 127 Pa, the fresh air fan needs to be able to deliver 500 CMH of airflow at 127 Pa. Therefore, we can select a fan with 150 Pa of external static pressure.

Duct Static Pressure Excel Calculator

Calculating the static pressure in a duct is a very lengthy process. But, if we’re able to create an Excel calculator for duct static pressure calculation, we can speed up the process dramatically. However, the selection of the duct fitting loss coefficient is most likely to remain manual.

Build Your HVAC Knowledge with a Structured Learning Path

If this guide helped you understand the topic, the next step is to learn HVAC in a more organized way. The HVAC Learning Hub helps you choose the right path based on your goal, whether you want self-paced courses, membership access, corporate training, or 1-to-1 mentorship.

Need project-specific advice, design, or troubleshooting support? View HVAC Engineering Services.

Leave a Reply

Your email address will not be published. Required fields are marked *

This site uses Akismet to reduce spam. Learn how your comment data is processed.

3 Comments

  1. Duct section No 13 : Flexible Duct size 200mm, with length 1 meter and air flow 500 CMH (Cubic meters per hour). Your pressure loss calculation is 0.72 Pa. I thing this value (0.72 Pa) is to low for 1 meter of flexible duct 200mm with 500 CMH (500*1.7= 850 CFM). 1.8 Pa is more reasonable value for uncompressed flexible duct of 200mm diameter. We usually use flexible ducts and about 300 CMH is the limit for 200mm diameter with 0,68 Pa/m.
    Your sincerely
    Vasilis Chatzinikolaou
    Electrical Engineer

    1. Hi Vasilis,

      Yes, I checked back the calculation and the flexible duct (uncompressed) supposed to be 1.78 Pa. So, I’ve corrected it. Thanks for pointing out.

      Regards,
      Yu