{"id":20167,"date":"2024-03-22T14:49:38","date_gmt":"2024-03-22T06:49:38","guid":{"rendered":"https:\/\/aircondlounge.com\/?p=20167"},"modified":"2024-03-26T12:03:24","modified_gmt":"2024-03-26T04:03:24","slug":"fire-damper-installation-configuration-and-joint-method","status":"publish","type":"post","link":"https:\/\/aircondlounge.com\/fire-damper-installation-configuration-and-joint-method\/","title":{"rendered":"Fire Damper Installation, Configuration and Joint Method"},"content":{"rendered":"\n

Fire dampers are one of the most critical components in HVAC. They prevent fire from spreading from one room to the other rooms. However, incorrect installation can lead to a fire damper malfunction and wrong configuration and joint method can hinder the inspection work.<\/p>\n\n\n\n

Many engineers don’t pay enough attention to how their fire dampers are configured, connected and installed in wall and slab openings, leading to their fire dampers not doing what they’re supposed to do in critical situations.<\/p>\n\n\n\n

Most of the time, the configuration, size and joint method of a fire damper are decided based on “as long as it fits into the duct”. Now, we should revisit how fire dampers are supposed to be installed.<\/p>\n\n\n\n

What is a Fire Damper?<\/h2>\n\n\n\n

To understand why fire dampers should be installed in certain ways, we must first understand what is a fire damper and what it supposed to do.<\/p>\n\n\n\n

In HVAC, large air conditioning ducts often need to penetrate through walls and slabs. We usually locate the air handling unit (AHU) in a dedicated room and run the duct toward the room that needs air conditioning. So, it is inevitable that one or more wall penetrations are required.<\/p>\n\n\n\n

Whenever a duct penetrates through a wall, the penetration point which we call duct opening or wall opening, must have a fire damper.<\/p>\n\n\n\n

In case of a fire outbreak, the fire damper will close to prevent the fire from spreading to the adjacent room. In fire protection, this is known as fire compartmentation<\/a>.<\/p>\n\n\n\n

So, most of the time, any wall penetration must have a fire damper, unless both rooms (before and after the penetration) are not a fire compartment.<\/p>\n\n\n\n

If we’re dealing with offices, hotels and hospitals, fire dampers are certainly required.<\/p>\n\n\n\n

Now, the concern is air conditioning ducts are usually not fire-rated<\/a>. So, during a fire, they may collapse under the immense heat. If the fire damper is just slotted inside the duct, the collapse could pull the fire damper down, leaving a hole at the wall penetration point.<\/p>\n\n\n\n

That’s why we need to make sure not just that there is a fire damper in the wall opening, but also that the fire damper is properly installed.<\/p>\n\n\n\n

Fire Damper Installation in Wall Penetration<\/h2>\n\n\n\n

When a duct needs to penetrate through a wall, we typically make an opening about 50mm (2″) all-round wider than the duct size. For example, if the duct size is 1500x300mm, the wall opening size is 1600x400mm.<\/p>\n\n\n\n

After the wall opening is done, we put a duct collar (sleeve) that’s already wrapped with a layer of insulation into the wall. The duct collar may not fit perfectly with some loose space but it’s fine because we can seal up the extra space with cement and stones later on.<\/p>\n\n\n